The SSE SPS series inverters have a modern industrial look and are built to last. With over 17 years experience manufacturing industrial electrical products and power quality equipment based on world class R&D and technology you can be confident of high quality and outstanding performance backed by an international after sales support team.
SPS1K5TL | SPS2K2TL | SPS3KTL-B | |
Input (DC) | |||
Max. DC power (W) | 1800 | 2500 | 3250 |
Max. DC voltage (V) | 500 | ||
Starting voltage (V) | 100 | ||
MPPT operating voltage range (V) | 120- 450 | ||
Rated power voltage range (V) | 180 - 450 | 180 - 450 | 200 - 450 |
Number of MPPT/ strings per MPPT | 1/1 | 1/1 | 1/2 |
Max. DC current (A) per MPPT x number of MPPT | 10x1 | 11x1 | 15x1 |
DC switch | No | ||
DC terminal | SUNCLIX water-proof terminal | ||
Output (AC side) | |||
Rated power (W) | 1500 | 2200 | 3000 |
Max. AC current (A) | 7.5 | 11 | 15 |
AC voltage range | 180~270Vac | ||
Grid frequency | 50Hz(47~51.5Hz) / 60Hz(57~61.5Hz) | ||
Power factor | ≥0.99(at rated power) | ||
THDI | < 3% (at rated power) | ||
AC connection | Single-phase (L, N, PE) | ||
Efficiency | |||
Max.efficiency | 96.90% | 97.20% | 97.30% |
Euro-efficiency | 96.00% | 96.10% | 96.30% |
MPPT efficiency | 99.9% | ||
Display and Communication | |||
Display | 3.5 inch LCD display, backlit display | ||
System language | English, German, Dutch, Chinese | ||
Communication mode | RS485(Standard); WiFi, Ethernet(Optional) | ||
Mechanical Data | |||
Dimension (H x W x D mm) | 460x328x172 | ||
Weight (kg) | ≤16.5 | ||
Cooling | Natural cooling, no fans | ||
General Data | |||
Protection degree | IP65 | ||
Consumption at night | <1W | ||
Topology | Transformerless | ||
Ambient temperature | -25℃~+60℃, derate over 45℃ | ||
Relative humidity | 0~95%, no condensation | ||
Protection | DC isolation monitoring, DC monitoring, grounding fault monitoring, grid monitoring, island protection, over voltage, short circuit, etc. | ||
Warranty | 5/10 years | ||
Certifications | TÜV, CE, VDE0126-1-1(VDE-AR-N4105), G83/1, G59/2, C10/11, TF3.2.1, AS4777/3100, CQC,EN61000-6-1:4, EN61000-3-2:3, EN61000-11:12; IEC 62109-1:2010 | ||